Part 1 · Metrics
Five numbers that matter
Each is defined in a part of ISO/IEC 30134 (International Organization for Standardization / International Electrotechnical Commission), the international series on data centre key performance indicators. Cards marked EU reported are among the four indicators EU data centres must report under Delegated Regulation (EU) 2024/1364; Carbon Usage Effectiveness is not one of them.
PUE, Power Usage Effectiveness
EU reportedPower Usage Effectiveness
How much of the site’s energy reaches the information technology (IT) equipment rather than cooling, power losses and lighting.
Total data centre energy ÷ IT equipment energy. 1.0 would mean no overhead at all.
With AI racks: Liquid cooling can bring it down, but it says nothing about whether the graphics processing units (GPUs) are doing useful work.
ISO/IEC 30134-2 · Source: European Commission: Commission Delegated Regulation (EU) 2024/1364 on the first phase of the establishment of a common Union rating scheme for data centres (read 2026-11-08)
WUE, Water Usage Effectiveness
EU reportedWater Usage Effectiveness
How much water the site uses for each unit of IT energy.
Water taken in ÷ IT equipment energy, in litres per kilowatt-hour.
With AI racks: Evaporative cooling improves PUE but uses water; closed-loop liquid cooling uses little water but can need more energy in hot climates.
ISO/IEC 30134-9 · Source: European Commission: Commission Delegated Regulation (EU) 2024/1364 on the first phase of the establishment of a common Union rating scheme for data centres (read 2026-11-08)
CUE, Carbon Usage Effectiveness
Carbon Usage Effectiveness
How much carbon dioxide the site’s energy use emits for each unit of IT energy.
Carbon dioxide emissions from the data centre’s energy ÷ IT equipment energy, in kilograms per kilowatt-hour.
With AI racks: Set mostly by the grid and the power contracts, not the building: a low PUE on a fossil-heavy grid still gives a poor CUE.
ISO/IEC 30134-8 · Source: ISO/IEC: ISO/IEC 30134-8 Carbon usage effectiveness (CUE) (read 2026-11-08)
ERF, Energy Reuse Factor
EU reportedEnergy Reuse Factor
The share of the site’s energy that is reused outside it, usually as heat for a district heating network.
Energy reused outside the data centre ÷ total data centre energy, from 0 to 1.
With AI racks: Warm-water liquid cooling returns hotter water than air cooling, which makes the heat far easier to sell.
ISO/IEC 30134-6 · Source: European Commission: Commission Delegated Regulation (EU) 2024/1364 on the first phase of the establishment of a common Union rating scheme for data centres (read 2026-11-08)
REF, Renewable Energy Factor
EU reportedRenewable Energy Factor
The share of the site’s energy that comes from renewable sources.
Renewable energy ÷ total data centre energy, from 0 to 1.
With AI racks: Large AI sites usually buy renewable energy by contract rather than generate it on site, so check what is being counted.
ISO/IEC 30134-3 · Source: European Commission: Commission Delegated Regulation (EU) 2024/1364 on the first phase of the establishment of a common Union rating scheme for data centres (read 2026-11-08)
Two figures can only be compared when they use the same definition, the same measurement points and the same period. A design-stage PUE and a measured annual PUE are not the same number.